| 1. | Water is the preferred media for heating coils.
Steam or electric heating coils must be discussed with Capital Projects
(CP). |
| |
| 2. | Provide hot water heating coils with copper
tubing and copper or aluminum fins. |
| |
| 3. | If steam is selected, provide distributing type coils.
Take particular care with the piping, trap and control installation details to prevent flooding of
the coils with condensate. |
| |
| 4. | Heating coils shall have a maximum of 12 fins per inch.
Use of this spacing reduces early coating with airborne dust, eventual plugging and facilitates
cleaning when necessary. |