| 2. | All design work shall be done by a licensed fire protection
engineer using separate 1/8" = 1' 0" minimum scale drawings for fire sprinklers and fire alarm
system. Before starting design work discuss the extent and type of fire protection system required
with the Campus Fire Marshal. Design/build specifications will be considered for small remodeling
projects only; discuss with Capital Projects (CP). |
| |
| 3. | In high-content-value areas, or where water damage must
be kept to a minimum, consider the use of a dry pipe system with early alarm and pre-activated system
charging control, on-off cycling heads or on-off cycling system. See Division 16 and discuss with
Capital Projects (CP) and Campus Fire Marshal. |
| |
| 4. | Specify a separate maintenance air compressor for any
dry pipe sprinkler system. To check for excessive air compressor operating time, install a digital
operating time clock reading to minimum of 999 hours, together with a recorder capable of totaling the
frequency of operation up to 999 cycles in motor electric service. Mount time clock adjacent to
compressor in a visible location. Where available, provide a cross connection, with pressure reducing
and check valve to the building compressed air system. Set for the minimum low pressure in the
sprinkler system. Install discharge filter for oil and water removal ahead of pressure regulating
valve. |
| |
| 5. | Discuss type of protection and alarm system for special
areas such as computer rooms, tape storage areas, free access floor systems, paint or solvent storage
rooms, transformer vaults, etc., with Capital Projects (CP) and Campus Fire
Marshal. |
| |
| 6. | Coordinate location of each sprinkler head with
reflected ceiling plan, including lighting and diffuser/grille layout. |
| |
| 7. | Coordinate the location, signage, keying, and access of
fire sprinkler shutoff and zone valves with Capital Projects (CP) and the Campus
Fire Marshal. Access and signage shall be obvious. Visibility shall not be blocked by
equipment. |
| |
| 8. | Show a Gamewell, model PRS, or equivalent, water flow
switch for each floor or sprinkler zone where a shunt type box is used. Switch shall have one
normally open and one normally closed contact. Specify alarm wiring in Division 16. |
| |
| 9. | Show a test valve and drain piping for each flow switch.
Terminate drain pipe at an approved receptor. Show the receptor on the plumbing and sprinkler
plans. |
| |
| 10. | Coordinate location of drains shown on plumbing
drawings with requirements of fire sprinkler system. Show drain locations on fire sprinkler
drawings. |
| |
| 11. | Guards shall be installed on any heads subject
to possible damage. |
| |
| 12. | For fire alarms and signal system components,
see Division 16. |
| |
| 13. | For alarm identification, see Division 16. |